Drilling & Tapping Information

Full Line Catalog

For Corporation Valves having a Jones® 110 Compression Connection (Super Grip) outlet

 

Valve size (nominal)

(If two numbers: Inlet x Outlet)

1/2"

3/4"

3/4" x 1"

1"

1-1/2"

2"

CTS

CTS

IPS PE

CTS

IPS PE

CTS

IPS PE

CTS

CTS

Maximum size drill or shell cutter

AWWA IP

7/16"

11/16"

11/16"

11/16"

11/16"

7/8"

7/8"

1-7/16"

1-3/4"*

CC (AWWA taper)

7/16"

11/16"

11/16"

11/16"

11/16"

15/16"

15/16"

1-7/16"

1-15/16"*

Mega-Cut™/E-5 machine adapter nipple

63796

52019

508919

36750

508920

36750

508920

501949

508199

D-5 machine adapter nipple

37900

37902

508917

37903

508918

37903

508918

597644

507645

Tru-Cut/PL-2 machine adapter nipple for use on 1.125" max. wall PVC

 

-

 

507632

 

509050

 

507633

 

509051

 

507633

 

509051

 

-

 

-

Combined drill and tap size

1/2"

3/4"

3/4"

1"

1-1/2"

2"

B-101/B-100 inserting tool

680598

680600

680688

680601

680689

680601

680689

-

-

A-3 inserting tool

-

-

-

-

-

680601

680689

680421

680422

*Ball Corporation valves IP and CC inlet: 1-7/8" maximum.

For Corporation Valves having a Pack Joint Connection outlet

Valve size (nominal)

(If two numbers: Inlet x Outlet)

3/4"

3/4" x 1"

1"

1-1/2"

2"

CTS

IPS

CTS

IPS

CTS

IPS

CTS

IPS PE

IPS

CTS

IPS PE

IPE PVC

 

Maximum size drill or shell cutter

AWWA IP

11/16"

-

11/16"

-

7/8"

-

1-7/16"

1-7/16"

-

1-3/4"*

1-3/4"*

-

CC

(AWWA taper)

11/16"

-

11/16"

-

15/16"

-

1-7/16"

1-7/16"

-

1-15/16"*

1-15/16"*

-

Mega-Cut™/E-5 machine adapter nipple

52019

508919

36750

682256

36750

682256

501949

508199**

682257

508199

682258

682258

D-5 machine adapter nipple

37902

508917

37903

682259

37903

682259

507644

507645**

682033

507645

682034

682034

Tru-Cut/PL-2 machine adapter nipple for use on 1.125" max. wall PVC

 

507632

 

509050

 

507633

 

-

 

507633

 

-

 

-

 

-

 

-

 

-

 

-

 

-

Combined drill and tap size

3/4"

3/4"

1"

1-1/2"

2"

B-101/B-100 inserting tool

680600

-

680601

680609

-

-

-

-

-

-

-

-

A-3 inserting tool

-

-

-

-

680601

680689

680421

-

-

680422

-

-

*Ball Corporation valves IP and CC inlet: 1-7/8" maximum.

For Corporation Valves having a Copper Flare Connection outlet

Valve size (nominal)

(If two numbers: Inlet x Outlet)

1/2"

1/2" x 3/4"

5/8" x 3/4"

3/4"

3/4" x 1"

1"

1-1/4"

1-1/2"

2"

Maximum size drill or shell cutter

AWWA IP

7/16"

7/16"

9/16"

11/16"

11/16"

7/8"

1-1/8"

1-7/16"

1-3/4"

CC (AWWA taper)

7/16"

7/16"

9/16"

11/16"

11/16"

15/16"

1-3/16"

1-7/16"

1-15/16"

Mega-Cut™/E-5 machine adapter nipple

63796

52019

52019

52019

36750

36750

682256

501947

508201

D-5 machine adapter nipple

37900

37902

37902

37902

37903

37903

682259

37905

37906

Tru-Cut/PL-2 machine adapter nipple for use on 1.125" max. wall PVC

 

-

 

-

 

-

 

507632

 

507633

 

507633

 

-

 

-

 

-

Combined drill and tap size

1/2"

1/2"

5/8"

3/4"

3/4"

1"

1-1/4"

1-1/2"

2"

B-101/B-100 inserting tool

680598

680600

680600

680600

680601

680601

-

-

-

A-3 inserting tool

-

-

-

-

-

680601

680602

88640

88641

For Corporation Valves having a Female I.P. thread outlet

Valve size (nominal) (If two numbers: Inlet x Outlet)

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

 

Maximum size drill or shell cutter

AWWA IP

7/16"

11/16"

7/8"

1-1/8"

1-7/16"

1-3/4"

CC (AWWA taper)

7/16"

11/16"

15/16"

-

1-7/16"

1-15/16"

Mega-Cut / E-5 machine adapter nipple

36967

36920

36918

36733

503435

78907

D-5 machine adapter nipple

-

33556

36323

36195

36196

36188

Tru-Cut / PL-2 machine adapter nipple for use on 1.125" max wall PVC

 

-

 

538275

 

538276

 

-

 

-

 

-

Combined drill and tap size

1/2"

3/4"

1"

1-1/4"

1-1/2"

2"

B-101/B-100 inserting tool

680630

680631

680632

-

-

-

A-3 inserting tool

-

-

680632

61212

61213

61214

For Corporation Valves having a Male I.P. thread outlet

Valve size (nominal) (If two numbers: Inlet x Outlet)

3/4"

1"

1-1/4"

1-1/2"

2"

 

Maximum size drill or shell cutter

IP

11/16"

7/8"

1-1/8"

1-7/16"

1-3/4"

CC (AWWA taper)

11/16"

15/16"

-

1-7/16"

1-15/16"

Mega-Cut / E-5 machine adapter nipple

36919

36917

36928

501948

508200

D-5 machine adapter nipple

36910

36911

36912

36913

36525

Tru-Cut / PL-2 machine adapter nipple for use on 1.125" max wall PVC

507630

507631

-

-

-

Combined drill and tap size

3/4"

1"

1-1/4"

1-1/2"

2"

B-101/B-100 inserting tool

36910

36911

36912

36913

36525

A-3 inserting tool

-

680596

680597

83065

83066

For Corporation Valves having an increasing Male I.P. thread outlet

Valve size (nominal) (If two numbers: Inlet x Outlet)

1/2"

5/8"

3/4"

1"

1-1/4"

1-1/2"

2"

 

Maximum size drill or shell cutter

IP

7/16"

9/16"

3/4"

15/16"

-

1-7/16"

1-3/4"

CC (AWWA taper)

7/16"

9/16"

11/16"

15/16"

1"

1-7/16"

1-15/16"

Mega-Cut / E-5 machine adapter nipple

36919

36919

36917

36928

501948

508200

-

D-5 machine adapter nipple

-

-

36911

36912

36913

36525

36526

Combined drill and tap size

1/2"

5/8"

3/4"

1"

1-1/4"

1-1/2"

2"

B-101/B-100 inserting tool

680595

680595

680596

680597

-

-

-

A-3 inserting tool

-

-

-

680597

83065

83066

83157

 